Contact Dwyer Sales Department: 1-201-419-6120  |  dwyer@nciweb.com


Dwyer Series FIP Pulse Input Flow Indicator

Flow Rate and Totalization

The FIP Series are flow rate/totalizer/batch controllers ideal for almost any flow application involving a pulse signal. They display both flow rate and total on an easy to read 7 segment LED display that provides up to 4-1/2 digits of rate display and 6 digits of total display. The pulse input meters accept pulse, open collector, TTL or square wave inputs. The meters also provide a loop power supply to drive the sensor.

For applications requiring more than just a display of rate or total, these meters can be equipped with two relays and a 4-20 mA retransmission output. The relays can be used for alarming based on the flow rate or for simple batch controlling based on the flow total.

The relays can also be used for applications beyond flow. For instance, they can be programmed for alternation making these products ideal for pump-control applications.

Specifications:
Inputs: (Field Selectable) Pulse: Pulse or Square Wave 0-5 V or 0-12 V @ 30 kHz max.; TTL; Open Collector 4.7 KΩ pull-up to 12 V @ 30 kHz; Switch Contact 4.7 KΩ pull-up to 12 V @ 40 Hz.
Display: 6 digit, 7 segment 0.56˝ (14.2 mm) high; Rate: -19,999(0) to 29,999(0) with selectable extra zero; Total: 0 to 999,999; automatic lead zero blanking.
Accuracy: ±0.1% F.S., ±0.004 mA.
Supply Voltage: 115 or 230 VAC ±10%, 50/60 Hz.
Power Consumption: 12 VA.
Enclosure: 1/8 DIN, high impact plastic.
Operating Temperature: 32 to 140ºF (0 to 60ºC).
Alarm Points: 0 or 2.
Alarm Output Relay Ratings: 2 SPDT (form C), rated 2 A @ 30 VDC or 2 A @ 250 VAC resistive, 1/14 hp @ 125/250 VAC for inductive.
Alarm Point Deadband: 0 to 100% of full scale, user selectable.
Isolation: 1500 VAC.
Loop Power Supply: Isolated 12 VDC @ 50 mA or 24 VDC ±5% @ 20 mA, regulated. Maximum loop resistance is 1200Ω.
Weight: 16 oz (454 g).
Front Panel Rating: NEMA 4X, Panel gasket provided.
Features:
  • Pulse, open collector, NPN, PNP, TTL, switch, or square wave inputs
  • Full six digit display for total, 4-1/2 digit + extra zero for rate
  • Display in engineering units; rate per second, minute, or hour
  • K-factor, internal, or external calibration
  • Scale without a calibrator or calibrate with a signal source
  • 11-point linearization for non-linear inputs
  • Low-flow cutoff
  • NEMA 4X front panel
  • 12 or 24 VDC field selectable sensor power supply standard
  • Quick preset change feature for batch control
  • 2 relays and 4-20 mA output options
Popular Models:
Model Number Input Output 1 Output 2 Power
 FIP-2100 Analog None None 115 VAC
 FIP-2110 Analog 2 Relays None 115 VAC
 FIP-2111 Analog 2 Relays (1) 4-20 mA 115 VAC
 FIP-2200 Analog None None 230 VAC
 FIP-2210 Analog 2 Relays None 230 VAC
 FIP2211 Analog 2 Relays (1) 4-20 mA 230 VAC
Previous Page