Dwyer Series 8500 Temperature/Process
Control
|
1/8 DIN, Microprocessor Based,
Horizontal or Vertical Format, Fully Programmable |
|
The Dwyer Series 8500 Temperature/Process
Control provides an impressive selection in a compact,
economical 1/8 DIN package. Choose from two case styles
in horizontal or vertical formats. Features include
on-off, time proportioning, proportional, PI, PD or
full PID control - fully programmable from the front
panel - or use Self-Tune® PID. Inputs are selectable
from a variety of thermocouple types including J, ,
T, E, N or L; DIN NIST or Ni RTD's. Output choices include
solid state relay, mechanical relay, 5 VDC - ideal for
driving an external SSR - or isolated 4-20 mA proportional
current. An optional programmable alarm provides a full
array of alarm action configurations including high
alarm, low alarm and high/low guardband alarm. Manual
reset, power-up inhibit and power interrupt reset provide
additional alarm flexibility. A water and corrosion
resistant front panel (NEMA 4X, IP65), input fault timer,
digital input filter, Self-Tune® ramp to setpoint, four
password protected security levels and °F or °C display
selection are all standard. Entire electronics package
is easily field replaceable without wiring changes thanks
to the removable front panel. |
|
Model
No.1
|
Alarm
|
Input
|
Output 2 |
D85011-(1)(0)
D85012-(1)(0)
D85013-(1)(0)
D85015-(1)(0)
D85021-(1)(0)
D85022-(1)(0)
D85023-(1)(0)
D85025-(1)(0)
D85111-(1)(0)
D85112-(1)(0)
D85113-(1)(0)
D85115-(1)(0)
D85121-(1)(0)
D85122-(1)(0)
D85123-(1)(0)
D85125-(1)(0)
|
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
|
Thermocouple
Thermocouple
Thermocouple
Thermocouple
RTD
RTD
RTD
RTD
Thermocouple
Thermocouple
Thermocouple
Thermocouple
RTD
RTD
RTD
RTD
|
SSR
5 VDC
Relay
4-20 mA
SSR
5 VDC
Relay
4-20 mA
SSR
5 VDC
Relay
4-20 mA
SSR
5 VDC
Relay
4-20 mA
|
|
|
|
1 Specify suffix 1 for horizontal
or 0 for vertical mounting.
2 When
ordering a control to operate contractor or solenoid
loads greater than 100 mA, select the SSR output instead
of the Relay. If the relay is selected, order part number
A-600. R/C snubber. |
|
PHYSICAL DATA |
Input
Impedance: |
|
Thermocouple
+ 3 megohms minimum, RTD current =
200 A
maximum |
Sensor
Break or
Short Protection: |
|
De-energizes
control output to protect system |
Setpoint
Range: |
|
Selectable |
Display: |
|
Two
4 digit, 7 segment LED; 0.4" (10
mm) high - horizontal models; 0.3" (7.62
mm) high -vertical models |
Control
Action: |
|
Selectable
for Reverse (usually heating) or Direct
(usually cooling) |
Accuracy: |
|
±0.25%
of span, ±1 degree |
Resolution: |
|
1
degree or 0.1 degree |
Temperature
Stability: |
|
2.3V/°F
(4 V/°C)
typ., 4.5 V/°F
(8 V/°C)
maximum |
Common
Mode Rejection: |
|
140
db minimum at 60 Hz |
Normal
Mode Rejection: |
|
65
db typical, 60 db at 60 Hz |
Isolation: |
|
Relay
and SSR outputs; 1500 VAC. 0-20 mA
output; 500 VAC. 5 VDC output is not
isolated |
Power
Consumption: |
|
5
VA maximum |
Supply
Voltage: |
|
100
to 240 VAC nominal, +10%-15%, 50 to
400 Hz, single phase; 132 to 240 VDC
+10%-20% |
Operating
Temperature Range: |
|
14
to 131°F (-10 to 55°C) |
Storage
Temperature Range: |
|
-40
to 176°F (-40 to 80°C) |
Humidity
Range: |
|
0
to 90% up to 104°F (40°C) non-condensing,
10 to 50% at 131°F (55°C) |
Memory
Backup: |
|
Non-volatile
memory. No batteries required |
Control
Output Ratings: |
|
SSR: 2.5
A at 240 VAC resisting at 77°F
(25°C). De-rate to 1.25 A at 130°F
(55°C)
Relay: SPDT, 10 A at 240
VAC resistive
Alarm Relay: SPST, 3 A
at 240 VAC resistive
Switched Voltage (non-isolated): 5
VDC at 20 mA
Proportional Current: 0-20
mA DC, scaleable into 600 ohms maximum.
|
Weight: |
|
10
oz. (369 g) |
|
|
|
|
|
SUGGESTED
SPECIFICATIONS |
Temperature/Process Controller
shall be 1/8 DIN (horizontal)(vertical), microprocessor based
with two four digit LED displays for setpoint, alarm status
and °F or °C. Input shall be (selectable J, K, T, E, N or L
thermocouple)(DIN-RTD). Output shall be (SSR)(5 VDC)(Relay)(Isolated
4-20 mA) programmable for manual or automatics Self-Tune® PID
control (with)(without) alarm. Front panel shall be designed
to meet NEMA-4X, IP 65 ratings for weather and corrosion resistance.
Accuracy shall be ±0.25% of span, ±1 degree. Temperature/Process