| **** THIS PRODUCT IS NO LONGER OFFERED - CHECK WITH US FOR A REPLACEMENT **** |
| |
Series 676 Duct Pressure
Transmitter
|
| ±1%
FS Accuracy, NEMA 4 (IP56) Enclosure, Three Field Selectable
Ranges |
| |
Lower installation costs
with the Series 676 Duct Pressure Transmitter. The Series 676
Transmitter incorporates a presure sensor and a static pressure
tip into a single unit, eliminating the need for costly control
panels and reducing installation time. Each transmitter has
three (3) field selectable pressure ranges.
A micro-machined glass-on silicon capacitance sensor provides
a high level, fully conditioned and temperature compensated
4-20mA output. Rugged NEMA 4 (IP56) enclosure with gasketed
cover protects the electronics and sensing element from condensation,
corrosion and dust. Units also feature shore circuit and reverse
polarity protection. |
| |
 |
| |
| --PHYSICAL
DATA - GENERAL |
| |
- Media Compatibility: Clean dry air or any inert
gas.
- Accuracy: ±1% FS (includes non-linearity, hysteresis,
and non-repeatability).
- Overpressure: 10 psid.
- Output: 4-20mA, 2-wire.
- Supply Voltage: 12-40 VDC.
- Loop Resistence: 3000 Ohms max @ 40 VDC
- Stability: Less than 1% FS/year.
- Operating Temperature Range: 0 to 175°F (-18 to
80°C).
- Operating Relative Humidity: 10 to 90% RH, non
condensing.
- Compensated Temperature Range: 25 to 150°F (-4
to 65°C).
- Thermal Errors: ±0.0125% F(0.02%/C).
- Response Time: 60 msec.
- Zero and Span Adjustment: ±15%, non-interactive.
- Wetted Parts: Aluminum alloy and nylon.
- Enclosure: Cold-Rolled Steel, NEMA 4 (IP56).
- Electrical Connections: Unpluggable screw terminal
block.
- Conduit Connection: 1/2". (22.3 mm) knockout.
- Weight: 1.0 lbs. (.45 kg).
|
| |
| Stock Model |
Range (inches w.c) |
| 676-11 |
0 to 5.0, 0 to 2.5, 0 to 1.25 |
| 676-21 |
0 to 15.0, 0 to 7.5, 0 to 3.75 |
| |
|
|
|